Skip to content
Menu

Substance data · Flammable liquid

m-Xylene: flash point and explosive limits

m-Xylene is a flammable liquid with a flash point of 25 °C. Its vapour is heavier than air and can ignite when mixed with air between 0.97 % and 7 % by volume.

  • LEL 0.97 %
  • UEL 7 %
  • Flash point 25 °C
  • AIT 465 °C
  • T1
  • IIA
C₈H₁₀m-Xylene
CAS
108-38-3
Molar mass
106.17 g/mol
Boiling point
139.1 °C
Relative density
3.67 ↓ heavier than air

Key values

Lower explosive limit (LEL)0.97 %by volume · 9,700 ppm
Upper explosive limit (UEL)7 %by volume
Flash point25 °CCLP: Category 3 (H226)
Autoignition temp. (AIT)465 °Ctemperature class at least T1
Gas groupIIAIIA, IIB and IIC equipment suitable
Relative density3.67air = 1 · heavier than air

Source: compilation of the IEC 60079-20-1:2010 data table and GESTIS (IFA, October 2026); the conservative end of the range (lowest LEL, flash point and AIT, highest UEL); gas group from GESTIS.

Explosive range and ppm values

m-Xylene can ignite when mixed with air between 0.97 % and 7 % by volume. Below the LEL the mixture is too lean to ignite, above the UEL too rich. A rich mixture re-enters the range when it is diluted with air, so concentrations above the upper limit are not safe either.

LEL 0.97 %UEL 7 % 0255075100Concentration in air, % by volume
Too lean: does not igniteExplosive rangeToo rich: enters the range when diluted with air

The lower explosive limit in ppm and g/m³. Useful to compare a gas detector's %LEL reading with ppm values in a measurement report.

Concentrationppmg/m³ (20 °C)
1 LEL (100 %LEL)9,70042.8
20 %LEL1,9408.56
10 %LEL9704.28

Convert another concentration in the LEL calculator

Lighter or heavier than air?

m-Xylene vapour is heavier than air: relative density 3.67 (air = 1). A release sinks and can collect in pits, trenches, drains and basements and travel a long way along the ground.

m-xylene upper ventpit
m-Xylene vapour sinks to the floor and flows into pits and trenches.

Flash point and liquid category

The flash point of m-xylene is 25 °C, the boiling point 139.1 °C.

With a flash point between 23 and 60 °C, it is a Category 3 flammable liquid under the CLP Regulation: H226 “Flammable liquid and vapour”, signal word “Warning”.

At room temperature (20 °C) no ignitable vapour concentration forms above the liquid. An explosive atmosphere can form when the liquid warms up to its flash point, for example in a hot process, a heated vessel or hot weather, or when it is sprayed under pressure (mist). A mist can ignite even below the flash point.

For another liquid, use the flammable liquid category calculator. The product label and safety data sheet apply; mixtures have different values.

Ex equipment selection

Autoignition temperature 465 °C. The maximum surface temperature of equipment in the zone must stay below it: all temperature classes (T1–T6) are suitable.

Temperature class
  1. T1450 °C suitable
  2. T2300 °C suitable
  3. T3200 °C suitable
  4. T4135 °C suitable
  5. T5100 °C suitable
  6. T685 °C suitable
Gas group
  1. IIA suitable
  2. IIB suitable
  3. IIC suitable

Gas group IIA: equipment marked IIA, IIB or IIC may be used. The equipment protection level (EPL: Ga, Gb, Gc) depends on the zone, not on the substance; the zone is decided in the explosion protection document from the release and the ventilation. Specific conditions in the certificate (X) and the ambient temperature range are checked separately.

Check an Ex label against m-xylene

Where is it found?

The most abundant isomer in commercial xylene; found as a solvent in paints, thinners and inks. Pure, it is used to make isophthalic acid.

Where these values sit in the explosion protection document

  • Substance properties. The first step of the document is to record these values, with their source, for every flammable substance on site.
  • Hazardous area classification. The lower explosive limit and the density are inputs to the release calculation and to the direction in which the zone extends.
  • Equipment selection. The temperature class and the gas group decide whether Ex equipment in the zone is suitable.

This page does not decide zones. The type and extent of a zone are calculated from where, how often and how much is released, and from the ventilation.

Sources

Explosive limits, autoignition temperature, gas group, flash and boiling point: compilation of the IEC 60079-20-1:2010 data table and GESTIS (IFA, October 2026); the conservative end of the range (lowest LEL, flash point and AIT, highest UEL); gas group from GESTIS.

The relative density is calculated from the molar mass (M / 28.96). The ppm and g/m³ values apply at 20 °C and 1 atm (molar volume 24.055 L/mol). The temperature class follows the rule that the surface temperature must stay below the autoignition temperature.

Molecule model: drawn from the PubChem 3D conformer (PubChem CID 7929).

This page is for information. For the substance on your site, the current safety data sheet (section 9) and the relevant standards apply. All substances are in the explosive limits table.

Frequently asked questions

What is the LEL of m-xylene in ppm?

0.97 % by volume, that is 9,700 ppm. 10 %LEL corresponds to 970 ppm and 20 %LEL to 1,940 ppm.

Is m-xylene heavier than air?

Yes, its vapour is heavier than air. Relative density 3.67 (air = 1): a release sinks and can collect in pits, trenches and drains.

Which Ex equipment is suitable for m-xylene?

Temperature class: any class from T1 to T6. Gas group: equipment marked IIA, IIB or IIC. The protection level (EPL) depends on the zone decided in the explosion protection document, not on the substance.

What is the flash point of m-xylene?

25 °C. Under CLP it is a Category 3 flammable liquid (H226).

Other flammable liquids

Related free tools

Planning a change at your Turkish site?

Tell us about the site, the planned change and your timeline. We usually reply within one working day.