Skip to content
Menu

Substance data · Flammable liquid

Acetone: flash point and explosive limits

Acetone is a flammable liquid with a flash point below room temperature (−20 °C). Its vapour is heavier than air and can ignite when mixed with air between 2.5 % and 14.3 % by volume.

  • LEL 2.5 %
  • UEL 14.3 %
  • Flash point −20 °C
  • AIT 465 °C
  • T1
  • IIA
C₃H₆OAcetone
CAS
67-64-1
Molar mass
58.08 g/mol
Boiling point
56.1 °C
Relative density
2.01 ↓ heavier than air

Key values

Lower explosive limit (LEL)2.5 %by volume · 25,000 ppm
Upper explosive limit (UEL)14.3 %by volume
Flash point−20 °CCLP: Category 2 (H225)
Autoignition temp. (AIT)465 °Ctemperature class at least T1
Gas groupIIAIIA, IIB and IIC equipment suitable
Relative density2.01air = 1 · heavier than air

Source: compilation of GESTIS, NIOSH and ISO/IEC 80079-20-1 data; the conservative end of the range between sources (lowest LEL and AIT, highest UEL).

Explosive range and ppm values

Acetone can ignite when mixed with air between 2.5 % and 14.3 % by volume. Below the LEL the mixture is too lean to ignite, above the UEL too rich. A rich mixture re-enters the range when it is diluted with air, so concentrations above the upper limit are not safe either.

LEL 2.5 %UEL 14.3 % 0255075100Concentration in air, % by volume
Too lean: does not igniteExplosive rangeToo rich: enters the range when diluted with air

The lower explosive limit in ppm and g/m³. Useful to compare a gas detector's %LEL reading with ppm values in a measurement report.

Concentrationppmg/m³ (20 °C)
1 LEL (100 %LEL)25,00060.4
20 %LEL5,00012.07
10 %LEL2,5006.04

Convert another concentration in the LEL calculator

Lighter or heavier than air?

Acetone vapour is heavier than air: relative density 2.01 (air = 1). A release sinks and can collect in pits, trenches, drains and basements and travel a long way along the ground.

acetone upper ventpit
Acetone vapour sinks to the floor and flows into pits and trenches.

Flash point and liquid category

The flash point of acetone is −20 °C, the boiling point 56.1 °C. As room temperature (20 °C) is above the flash point, an ignitable vapour can form above the surface of an open container or a spill.

With a flash point below 23 °C and boiling point above 35 °C, it is a Category 2 flammable liquid under the CLP Regulation: H225 “Highly flammable liquid and vapour”, signal word “Danger”.

For another liquid, use the flammable liquid category calculator. The product label and safety data sheet apply; mixtures have different values.

Ex equipment selection

Autoignition temperature 465 °C. The maximum surface temperature of equipment in the zone must stay below it: all temperature classes (T1–T6) are suitable.

Temperature class
  1. T1450 °C suitable
  2. T2300 °C suitable
  3. T3200 °C suitable
  4. T4135 °C suitable
  5. T5100 °C suitable
  6. T685 °C suitable
Gas group
  1. IIA suitable
  2. IIB suitable
  3. IIC suitable

Gas group IIA: equipment marked IIA, IIB or IIC may be used. The equipment protection level (EPL: Ga, Gb, Gc) depends on the zone, not on the substance; the zone is decided in the explosion protection document from the release and the ventilation. Specific conditions in the certificate (X) and the ambient temperature range are checked separately.

Check an Ex label against acetone

Where is it found?

Widely used as a solvent in paints, varnishes and adhesives, for cleaning and degreasing, and in laboratories.

Where these values sit in the explosion protection document

  • Substance properties. The first step of the document is to record these values, with their source, for every flammable substance on site.
  • Hazardous area classification. The lower explosive limit and the density are inputs to the release calculation and to the direction in which the zone extends.
  • Equipment selection. The temperature class and the gas group decide whether Ex equipment in the zone is suitable.

This page does not decide zones. The type and extent of a zone are calculated from where, how often and how much is released, and from the ventilation.

Sources

Explosive limits, autoignition temperature, gas group, flash and boiling point: compilation of GESTIS, NIOSH and ISO/IEC 80079-20-1 data; the conservative end of the range between sources (lowest LEL and AIT, highest UEL).

The relative density is calculated from the molar mass (M / 28.96). The ppm and g/m³ values apply at 20 °C and 1 atm (molar volume 24.055 L/mol). The temperature class follows the rule that the surface temperature must stay below the autoignition temperature.

This page is for information. For the substance on your site, the current safety data sheet (section 9) and the relevant standards apply. All substances are in the explosive limits table.

Frequently asked questions

What is the LEL of acetone in ppm?

2.5 % by volume, that is 25,000 ppm. 10 %LEL corresponds to 2,500 ppm and 20 %LEL to 5,000 ppm.

Is acetone heavier than air?

Yes, its vapour is heavier than air. Relative density 2.01 (air = 1): a release sinks and can collect in pits, trenches and drains.

Which Ex equipment is suitable for acetone?

Temperature class: any class from T1 to T6. Gas group: equipment marked IIA, IIB or IIC. The protection level (EPL) depends on the zone decided in the explosion protection document, not on the substance.

What is the flash point of acetone?

−20 °C. As room temperature is above it, an ignitable vapour can form above an open container or a spill. Under CLP it is a Category 2 flammable liquid (H225).

Other substances

Related free tools

Planning a change at your Turkish site?