Where the explosion risk comes from
Most solvent vapours are heavier than air and collect at floor level, in pits and in drains. Liquids whose flash point is below the ambient temperature, such as thinners, acetone, ethyl acetate and toluene, give off vapour continuously from an open surface. Low-conductivity liquids such as toluene and xylene become charged with static electricity as they flow and are poured.
Sources of release
- Decanting from drums and IBCs
- Filling and weighing point
- Open containers and mixing
- Pump and hose connections
- Spills and the containment sump
- Empty drum and waste solvent area
- Floor drains and pits
Liquid in closed, intact packaging does not release in normal operation. In areas used only for storage, the assessment therefore usually rests on a possible spill and on the ventilation.
What we look at closely
In a store the deciding factor is often not the quantity stored but the decanting. A small transfer from a drum into a can carries more vapour and static risk than hundreds of litres in closed packaging. We therefore establish, one by one, where transfers take place, with which containers, with what earthing and how often.
How we assess it
- Chemical inventory. Flash point, explosive limits and vapour density are taken from the safety data sheet of every product in the store. Products whose flash point is below the ambient temperature are separated out.
- Decanting and filling. Which liquid is transferred where, with which containers and how often is established on site or from your team's notes and photographs. Evaporation from open surfaces and possible spills are calculated.
- Ventilation. Natural or mechanical ventilation is measured or taken from documents. Because the vapour is heavy, how close the extract points and openings are to the floor is assessed separately.
- Zone decision. The decanting point, the spill area and the store as a whole are assessed separately. Drains and pits are included in the zone decision.
- Static electricity. The earthing arrangement, the container material and the filling rate for drums, funnels, IBCs and pumps are checked against the conductivity of the liquid.
Gaps worth checking
- Zones written for the store, with the decanting and filling point left out.
- No earthing clamp used when decanting from a drum into a can.
- Plastic cans, buckets and funnels used for liquids such as thinners.
- No check on whether a caged plastic IBC is suitable for a flammable solvent.
- Empty drums left with their bungs open. An empty drum is full of vapour.
- Ventilation openings only at ceiling level, although solvent vapour sinks to the floor.
- Drains and gullies left out of the assessment.
What we need from you
- List of stored products and their safety data sheets
- Layout of the store and the decanting area
- Monthly quantities used and decanted
- Ventilation data and any fan flow rate
- List of equipment such as pumps, scales and lighting, with any Ex certificates
- Earthing test report
What you receive
A chemical inventory with a screening table, decanting and spill calculations, and zone drawings for the store and the decanting area. With them come static electricity measures, a decanting instruction, an action plan and area rules for the store door.
Rules in your country
- Great Britain. Storage is part of the DSEAR risk assessment; HSE's guidance HSG51 covers the storage of flammable liquids in containers.
- Germany. The zones go into the Explosionsschutzdokument; storage in portable containers follows TRGS 510, and in fixed tanks TRGS 509.
- Netherlands. The zones go into the explosieveiligheidsdocument; the storage of packaged hazardous substances follows PGS 15.
- United States. Flammable liquid storage falls under OSHA 29 CFR 1910.106 and NFPA 30. On request we classify to NFPA 497 with the Division system.
- Türkiye. The zones go into the explosion protection document required by the 2013 regulation, and we work on site.
Questions
Our store holds only closed packages. Is an assessment still needed?
Yes, although the result is often a small zone or none at all. What matters is that the reasoning is written in the document, together with the conditions it depends on, such as no decanting in the store and measures against spills.
Water-based products are kept in the same store. Are they assessed too?
Yes. Every product is assessed from its safety data sheet. Non-flammable products and those with a high flash point are set aside with the reason, but they stay in the inventory.
We decant into plastic cans. Is that a problem?
The use of insulating plastic containers in a hazardous area is limited. It depends on the conductivity of the liquid, the size of the container and the zone. The report states which container may be used where, and the earthing arrangement.
This page is general information. The result for your site is set by calculations based on your site data.