Where the explosion risk comes from
In lead-acid batteries, especially towards the end of charging, water in the electrolyte is split and hydrogen is released. Hydrogen is very light, forms a flammable mixture with air over a wide range (about 4 to 75 per cent by volume) and can be ignited by a very small amount of energy.
Sources of release
- Battery cells during charging
- Battery lids and vent caps
- Accumulation below the ceiling
- Charger, plug and socket
- Maintenance and topping up
Lithium-ion batteries do not release hydrogen in normal charging. In a fault (thermal runaway) they can release flammable gases and cause a fire. The two battery types are assessed separately.
What we look at closely
The calculation is driven not by the highest current on the charger's label but by the gassing current at the end of charging, which depends on the battery type and the charging method. We therefore read the battery and charger labels separately, from photographs or on site, and take the number of batteries charged at the same time from the shift pattern. Because hydrogen rises, a high-level opening matters more for ventilation than a low one.
How we assess it
- Battery and charger data. Battery voltage, capacity and number of cells, and the charger types, are recorded from the labels. The number of batteries charged at the same time is established.
- Hydrogen calculation. The hydrogen released is calculated, and the ventilation required is compared with the method of the battery standards (EN IEC 62485 series).
- Ventilation. Whether charging takes place in an open hall or a separate room is established. Natural or mechanical ventilation and the openings are measured on site or taken from drawings and photographs.
- Zone decision. The space close to the batteries and the room as a whole are assessed separately, and the result is cross-checked with an independent method.
- Ignition sources. The position of chargers and sockets relative to the batteries, static electricity and work done during maintenance are assessed.
Gaps worth checking
- The charging area missing from the document altogether.
- Charging under racking, in enclosed corners or in rooms without ventilation.
- Ventilation openings only at low level, although hydrogen collects below the ceiling.
- Chargers mounted directly above the batteries.
- No check that mechanical ventilation runs whenever charging takes place.
- The document not updated after a change to lithium-ion batteries.
What we need from you
- List of trucks and batteries (photographs of the labels are enough)
- Charger labels
- Dimensions and layout of the charging area
- Ventilation data, including any fan flow rate
- Shift and charging pattern
What you receive
A calculation sheet for hydrogen, ventilation and zones, with the zone drawing. With them come area rules for the charging area, such as no naked flames or smoking and the checks before charging, and an action plan.
Rules in your country
- Great Britain. The charging area is part of the DSEAR risk assessment; the ventilation is checked with the method of the EN IEC 62485 series.
- Germany. The zones go into the Explosionsschutzdokument (§ 6(9) GefStoffV); the ventilation follows the EN IEC 62485 series.
- Netherlands. The zones go into the explosieveiligheidsdocument as part of the RI&E.
- United States. Charging of industrial truck batteries falls under OSHA 29 CFR 1910.178(g), and 1910.305(j)(7) asks for ventilation that prevents explosive mixtures from accumulating. On request we classify to NFPA 497 with the Division system.
- Türkiye. The zones go into the explosion protection document required by the 2013 regulation, and we work on site.
Questions
Do lithium-ion batteries need an assessment too?
Lithium-ion batteries do not release hydrogen in normal charging, so the explosive atmosphere assessment may reach a different result. Flammable gases that may be released in a fault, and the fire risk, are assessed separately. Where both types are used, each is assessed on its own.
There is a fan in the charging area. Is that enough?
The fan's flow rate is compared with the calculated need. Whether the fan runs whenever charging takes place, and what happens if it fails, are written into the report and the control plan.
The charging area is inside a large hall. Will there still be a zone?
In a large, well-ventilated hall the zone is often limited to the space close to the batteries. The result depends on the number of batteries, the charging current and the ventilation, and the calculation decides it.
This page is general information. The result for your site is set by calculations based on your site data.