Skip to content
Menu

Substance data · Flammable liquid

Dimethylformamide: flash point and LEL

Dimethylformamide is a flammable liquid with a flash point of 58 °C. Its vapour is heavier than air and can ignite when mixed with air between 1.8 % and 16 % by volume.

  • LEL 1.8 %
  • UEL 16 %
  • Flash point 58 °C
  • AIT 440 °C
  • T2
  • IIA
C₃H₇NODimethylformamide (DMF)
CAS
68-12-2
Molar mass
73.09 g/mol
Boiling point
152.8 °C
Relative density
2.52 ↓ heavier than air

Key values

Lower explosive limit (LEL)1.8 %by volume · 18,000 ppm
Upper explosive limit (UEL)16 %by volume
Flash point58 °CCLP: Category 3 (H226)
Autoignition temp. (AIT)440 °Ctemperature class at least T2
Gas groupIIAIIA, IIB and IIC equipment suitable
Relative density2.52air = 1 · heavier than air

Source: compilation of the IEC 60079-20-1:2010 data table and GESTIS (IFA, October 2026); the conservative end of the range (lowest LEL, flash point and AIT, highest UEL); gas group from GESTIS.

Explosive range and ppm values

Dimethylformamide can ignite when mixed with air between 1.8 % and 16 % by volume. Below the LEL the mixture is too lean to ignite, above the UEL too rich. A rich mixture re-enters the range when it is diluted with air, so concentrations above the upper limit are not safe either.

LEL 1.8 %UEL 16 % 0255075100Concentration in air, % by volume
Too lean: does not igniteExplosive rangeToo rich: enters the range when diluted with air

The lower explosive limit in ppm and g/m³. Useful to compare a gas detector's %LEL reading with ppm values in a measurement report.

Concentrationppmg/m³ (20 °C)
1 LEL (100 %LEL)18,00054.7
20 %LEL3,60010.94
10 %LEL1,8005.47

Convert another concentration in the LEL calculator

Lighter or heavier than air?

Dimethylformamide vapour is heavier than air: relative density 2.52 (air = 1). A release sinks and can collect in pits, trenches, drains and basements and travel a long way along the ground.

dimethylformamide upper ventpit
Dimethylformamide vapour sinks to the floor and flows into pits and trenches.

Flash point and liquid category

The flash point of dimethylformamide is 58 °C, the boiling point 152.8 °C.

With a flash point between 23 and 60 °C, it is a Category 3 flammable liquid under the CLP Regulation: H226 “Flammable liquid and vapour”, signal word “Warning”.

At room temperature (20 °C) no ignitable vapour concentration forms above the liquid. An explosive atmosphere can form when the liquid warms up to its flash point, for example in a hot process, a heated vessel or hot weather, or when it is sprayed under pressure (mist). A mist can ignite even below the flash point.

For another liquid, use the flammable liquid category calculator. The product label and safety data sheet apply; mixtures have different values.

Ex equipment selection

Autoignition temperature 440 °C. The maximum surface temperature of equipment in the zone must stay below it: T2, T3, T4, T5 and T6 are suitable; T1 is not, because the limit is not below the autoignition temperature.

Temperature class
  1. T1450 °C not suitable
  2. T2300 °C suitable
  3. T3200 °C suitable
  4. T4135 °C suitable
  5. T5100 °C suitable
  6. T685 °C suitable
Gas group
  1. IIA suitable
  2. IIB suitable
  3. IIC suitable

Gas group IIA: equipment marked IIA, IIB or IIC may be used. The equipment protection level (EPL: Ga, Gb, Gc) depends on the zone, not on the substance; the zone is decided in the explosion protection document from the release and the ventilation. Specific conditions in the certificate (X) and the ambient temperature range are checked separately.

Check an Ex label against dimethylformamide

Where is it found?

Used as a solvent in polyurethane coatings (synthetic leather), acrylic fibre production and pharmaceutical and chemical synthesis. It is toxic to reproduction: the health hazard is assessed separately. Commonly called DMF.

Where these values sit in the explosion protection document

  • Substance properties. The first step of the document is to record these values, with their source, for every flammable substance on site.
  • Hazardous area classification. The lower explosive limit and the density are inputs to the release calculation and to the direction in which the zone extends.
  • Equipment selection. The temperature class and the gas group decide whether Ex equipment in the zone is suitable.

This page does not decide zones. The type and extent of a zone are calculated from where, how often and how much is released, and from the ventilation.

Sources

Explosive limits, autoignition temperature, gas group, flash and boiling point: compilation of the IEC 60079-20-1:2010 data table and GESTIS (IFA, October 2026); the conservative end of the range (lowest LEL, flash point and AIT, highest UEL); gas group from GESTIS.

The relative density is calculated from the molar mass (M / 28.96). The ppm and g/m³ values apply at 20 °C and 1 atm (molar volume 24.055 L/mol). The temperature class follows the rule that the surface temperature must stay below the autoignition temperature.

Molecule model: Wikimedia Commons, DMF-3D-balls.png (public domain).

This page is for information. For the substance on your site, the current safety data sheet (section 9) and the relevant standards apply. All substances are in the explosive limits table.

Frequently asked questions

What is the LEL of dimethylformamide in ppm?

1.8 % by volume, that is 18,000 ppm. 10 %LEL corresponds to 1,800 ppm and 20 %LEL to 3,600 ppm.

Is dimethylformamide heavier than air?

Yes, its vapour is heavier than air. Relative density 2.52 (air = 1): a release sinks and can collect in pits, trenches and drains.

Which Ex equipment is suitable for dimethylformamide?

Temperature class: T2, T3, T4, T5 or T6 (T1 not suitable). Gas group: equipment marked IIA, IIB or IIC. The protection level (EPL) depends on the zone decided in the explosion protection document, not on the substance.

What is the flash point of dimethylformamide?

58 °C. Under CLP it is a Category 3 flammable liquid (H226).