Skip to content
Menu

Substance data · Flammable gas

Ammonia: explosive limits (LEL, UEL) and AIT

Ammonia is a gas lighter than air. Mixed with air it can ignite between 14 % and 33.6 % by volume.

  • LEL 14 %
  • UEL 33.6 %
  • AIT 630 °C
  • T1
  • IIA
NH₃Ammonia
CAS
7664-41-7
Molar mass
17.03 g/mol
Boiling point
−33.3 °C
Relative density
0.59 ↑ lighter than air

Key values

Lower explosive limit (LEL)14 %by volume · 140,000 ppm
Upper explosive limit (UEL)33.6 %by volume
Flash pointgasnot used for gases
Autoignition temp. (AIT)630 °Ctemperature class at least T1
Gas groupIIAIIA, IIB and IIC equipment suitable
Relative density0.59air = 1 · lighter than air

Source: compilation of GESTIS, NIOSH and ISO/IEC 80079-20-1 data; the conservative end of the range between sources (lowest LEL and AIT, highest UEL).

Explosive range and ppm values

Ammonia can ignite when mixed with air between 14 % and 33.6 % by volume. Below the LEL the mixture is too lean to ignite, above the UEL too rich. A rich mixture re-enters the range when it is diluted with air, so concentrations above the upper limit are not safe either.

LEL 14 %UEL 33.6 % 0255075100Concentration in air, % by volume
Too lean: does not igniteExplosive rangeToo rich: enters the range when diluted with air

The lower explosive limit in ppm and g/m³. Useful to compare a gas detector's %LEL reading with ppm values in a measurement report.

Concentrationppmg/m³ (20 °C)
1 LEL (100 %LEL)140,00099.1
20 %LEL28,00019.82
10 %LEL14,0009.91

Convert another concentration in the LEL calculator

Lighter or heavier than air?

Ammonia is lighter than air: relative density 0.59 (air = 1). A release rises and can collect under the ceiling, between beams and in enclosed upper spaces, so the position of a ventilation opening matters as much as its area.

ammonia upper ventpit
If ammonia leaks, it rises, collects under the ceiling and leaves through the upper vent.

The relative density applies to the substance at room temperature. Very cold releases, for example from an evaporating liquefied gas, can behave as heavier than air for a while.

Ex equipment selection

Autoignition temperature 630 °C. The maximum surface temperature of equipment in the zone must stay below it: all temperature classes (T1–T6) are suitable.

Temperature class
  1. T1450 °C suitable
  2. T2300 °C suitable
  3. T3200 °C suitable
  4. T4135 °C suitable
  5. T5100 °C suitable
  6. T685 °C suitable
Gas group
  1. IIA suitable
  2. IIB suitable
  3. IIC suitable

Gas group IIA: equipment marked IIA, IIB or IIC may be used. The equipment protection level (EPL: Ga, Gb, Gc) depends on the zone, not on the substance; the zone is decided in the explosion protection document from the release and the ventilation. Specific conditions in the certificate (X) and the ambient temperature range are checked separately.

Check an Ex label against ammonia

Where is it found?

Used as a refrigerant in industrial refrigeration: found in cold stores, food and beverage plants, fertiliser and chemical plants. It is toxic: besides its flammability, the toxic hazard is assessed separately.

Where these values sit in the explosion protection document

  • Substance properties. The first step of the document is to record these values, with their source, for every flammable substance on site.
  • Hazardous area classification. The lower explosive limit and the density are inputs to the release calculation and to the direction in which the zone extends.
  • Equipment selection. The temperature class and the gas group decide whether Ex equipment in the zone is suitable.

This page does not decide zones. The type and extent of a zone are calculated from where, how often and how much is released, and from the ventilation.

Sources

Explosive limits, autoignition temperature, gas group, flash and boiling point: compilation of GESTIS, NIOSH and ISO/IEC 80079-20-1 data; the conservative end of the range between sources (lowest LEL and AIT, highest UEL).

The relative density is calculated from the molar mass (M / 28.96). The ppm and g/m³ values apply at 20 °C and 1 atm (molar volume 24.055 L/mol). The temperature class follows the rule that the surface temperature must stay below the autoignition temperature.

This page is for information. For the substance on your site, the current safety data sheet (section 9) and the relevant standards apply. All substances are in the explosive limits table.

Frequently asked questions

What is the LEL of ammonia in ppm?

14 % by volume, that is 140,000 ppm. 10 %LEL corresponds to 14,000 ppm and 20 %LEL to 28,000 ppm.

Is ammonia heavier than air?

No. Relative density 0.59 (air = 1): a release rises and can collect under the ceiling.

Which Ex equipment is suitable for ammonia?

Temperature class: any class from T1 to T6. Gas group: equipment marked IIA, IIB or IIC. The protection level (EPL) depends on the zone decided in the explosion protection document, not on the substance.

What is the autoignition temperature of ammonia?

630 °C. A mixture touching a surface at this temperature can ignite without a flame or spark, so the surface temperature of equipment must stay below it (at least T1).

Other substances

Related free tools

Planning a change at your Turkish site?

Tell us about the site, the planned change and your timeline. We usually reply within one business day.